Omron E5CB PID Temperature Controller, 48 x 48mm, 1 Output Relay, 100 ? 240 V ac Supply Voltage ON/OFF

SKU: E5CB

Specifications

PRODUCT BRAND: ​
PRODUCT NAME: ​
Omron E5CB PID Temperature Controller, 48 x 48mm, 1 Output Relay, 100 ? 240 V ac Supply Voltage ON/OFF
PRODUCT NUMBER:
E5CB
AVAILABILITY: ​
On-Demand

DESCRIPTION

Power supply voltage100 to 240 VAC 50/60 Hz, 24 VAC 50/60 Hz, or 24 VDC
Operating voltage range85% to 110% of rated supply voltage
Power consumptionApprox. 3.5 VA (100 to 240 VAC)
Approx. 3.5 VA (24 VAC)
Approx. 2.5 W (24 VDC)
Sensor inputModels with thermocouple inputs
Thermocouple: K, J, T, R, or S (JIS C 1602-1995, IEC60584-1)
Models with platinum resistance thermometer inputs
Platinum resistance thermometer: Pt100 (JIS C 1604-1997, IEC60751)
Control
output
Relay outputSPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations,
minimum applicable load: 5 V, 10 mA
Voltage output
(for driving SSR)
Output voltage: 12 VDC +25%/-15% (PNP), max. load current: 21 mA, with short-circuit
protection circuit
Alarm
output
Relay outputSPST-NO, 250 VAC, 1 A (resistive load), electrical life: 100,000 operations, minimum
load: 5 V, 10 mA
Control methodON/OFF control or 2-PID control (with auto-tuning)
Setting methodDigital setting using front panel keys
Indication method7-segment digital display and individual indicators
Character height: 16.2 mm (PV)
Other functionsTemperature input shift, run/stop, protection functions, etc.
Ambient operating
temperature
-10 to 55°C (with no condensation or icing)/With a three-year guarantee: -10 to 50°C
Ambient operating humidity25% to 85%
Storage temperature-25 to 65°C (with no condensation or icing)

 

Input Ranges

Models with Thermocouple Inputs

 

Model
(temperature input)
Set valueInput typeRange
°C°F
TC input0K-200 to 1,300-300 to 2,300
1-20.0 to 500.00.0 to 900.0
2J-100 to 850-100 to 1500
3-20.0 to 400.00.0 to 750.0
4T-200 to 400-300 to 700
5-199.9 to 400.0-199.9 to 700.0
6R0 to 1,7000 to 3,000
7S0 to 1,7000 to 3,000

 

Default setting: 0
Applicable standards (K, J, T, R, S): JIS C1602-1995 and IEC 60584-1

Platinum Resistance Thermometer Input

 

Model
(temperature input)
Set valueInput typeRange
°C°F
Pt input8Pt100-200 to 850-300 to 1500
9-199.9 to 500.0-199.9 to 900.0

 

Default setting: 8
Applicable standards (Pt100): JIS C1604-1997 and IEC 60751

Alarm Types

Select alarm types out of the 11 alarm types listed in the following table.

 

SettingAlarm typePositive alarm
value (X)
Negative alarm
value (X)
Deviation alarm/
absolute value alarm
0No alarmOutput OFF
1Upper/lower limit
Always ONDeviation alarm
2Upper limit
Deviation alarm
3Lower limit
Deviation alarm
4Upper/lower range
Always OFFDeviation alarm
5 *2Upper/lower limit standby sequence ON
Always OFFDeviation alarm
6 *2Upper limit standby sequence ON
Deviation alarm
7 *2Lower limit standby sequence ON
Deviation alarm
8Absolute value upper limit
Absolute value alarm
9Absolute value lower limit
Absolute value alarm
10 *2Absolute value upper limit standby sequence ON
Absolute value alarm
11 *2Absolute value lower limit standby sequence ON
Absolute value alarm
12Do not set.

 

 

Note: 1. The default is 2.
2. Alarms with a Standby Sequence
The alarm is blocked until the first safe-state is reached.
Unwanted alarm during start-up are prevented.

 

Example: Deviation Lower Limit Standby Sequence ON
The standby sequence is cleared when the alarm OFF condition has been met.

E5CB Specifications 10

The standby sequence is started again when any of the following conditions is met.
• Operation is started (power is turned ON or operation is switched from stop to run).
• The alarm value is changed.
• The temperature input offset is changed.
• The set point is changed.

Characteristics

 

Indication accuracyThermocouple: (See note 1.)
(±0.5% of indicated value or ±1°C, whichever is greater) ±1 digit max.
Platinum resistance thermometer:
(±0.5% of indicated value or ±1°C, whichever is greater) ±1 digit max.
Influence of temperature
(See note 2.)
R and S thermocouple inputs: (±1% of PV or ±10°C, whichever is greater) ±1
digit max.
K, J, and T thermocouple inputs: (±1% of PV or ±4°C, whichever is greater) ±1
digit max.
Platinum resistance thermometer inputs: (±1% of PV or ±2°C, whichever is
greater) ±1 digit max.
Influence of voltage
(See note 2.)
Influence of EMS.
(at EN 61326-1)
Hysteresis0.1 to 999.9 (in units of 0.1) °C/°F
Proportional band (P)0.1 to 999.9 (in units of 0.1) °C/°F
Integral time (I)0 to 3999 s (in units of 1 s)
Derivative time (D)0 to 3999 s (in units of 1 s)
Control period0.5, 1 to 99 s (in units of 1 s)
Alarm setting range-1999 to 9999 (decimal point position depends on input type)
Input sampling period250 ms
Affect of signal source resistanceThermocouple: 0.1°C/Ω max. (100 Ω max.) (See note 3.)
Platinum resistance thermometer: 0.6°C/Ω max. (10 Ω max.)
Insulation resistance20 MΩ min. (at 500 VDC)
Dielectric strength2,800 VAC, 50 or 60 Hz for 1 min (between terminals with different charge)
Vibration
resistance
Malfunction10 to 55 Hz, 20 m/s2 for 10 min each in X, Y, and Z directions
Destruction10 to 55 Hz, 20 m/s2 for 2 hrs each in X, Y, and Z directions
Shock
resistance
Malfunction200 m/s2, 3 times each in X, Y, and Z directions
Destruction300 m/s2, 3 times each in X, Y, and Z directions
WeightController: Approx. 100 g, Mounting Bracket: Approx. 10 g
Degree of protectionFront panel: IP66
Rear case: IP20, Terminals: IP00
Memory protectionNon-volatile memory (number of writes: 100,000 times)
Conformed
standards
Certified standardsUL 61010-1, CSA C22.2 No. 1010-1
Applicable standardsEN61326, EN61010-1, IEC61010-1
VDE0106, Part 100 (Finger protection), when the terminal cover is mounted.
EMCEMI EN61326-1 (See note 4.)
Emission Enclosure: EN55011 Group1 Class A
Emission AC Mains: EN55011 Group1 Class A
EMS EN61326-1 (See note 4.)
Immunity ESD: EN61000-4-2
Immunity RF-interference: EN61000-4-3
Immunity Burst: EN61000-4-4
Conduction Disturbance Immunity EN61000-4-6
Immunity Surge: EN61000-4-5
Immunity Voltage Dip/Interrupting: EN61000-4-11

 

Note: 1. The indication accuracy of K and T thermocouples at a temperature of −100°C max. is ±2°C ±1 digit maximum.
The indication accuracy of the R and S thermocouples at a temperature of 200°C max. is ±3°C ±1 digit max.
2. Conditions: Ambient temperature: −10 to 23 to 55°C, Voltage range: −15% to ±10% of rated voltage
3. R, and S sensors: 0.2°C/Ω max. (100 Ω max.)
4. Industrial electromagnetic environment (EN/IEC 61326-1 Table 2)

USB-Serial Conversion Cable Specifications

 

Applicable OSWindows XP/Vista/7/8/8.1/10
Applicable softwareThermo Mini
Applicable modelsE5CB Series
USB interface standardUSB specification 1.1
DTE speed38,400 bps
Connector SpecificationsComputer: USB (Type A plug)
Temperature Controller: Special serial connector
Power supplyBus power (supplied from the USB host controller)
Power supply voltage5 VDC
Current consumption450 mA max.
Output voltage4.7±0.2 VDC (Supplied from USB-Serial Conversion Cable to the Temperature Controller.)
Output current250 mA max. (Supplied from USB-Serial Conversion Cable to the Temperature Controller.)
Ambient temperature0 to 55°C (with no condensation or icing)
Ambient humidity10% to 80%
Storage temperature-20 to 60°C (with no condensation or icing)
Storage humidity10% to 80%
Altitude2,000 m max.
WeightApprox. 120 g

 

Note: 1. A high-power port is used for the USB port.
2. A driver must be installed on the computer. Refer to the Instruction Manual included with the Cable for the
installation procedure.