Variable Speed Drive – ATV21 – 3kw NAHP – 480V – EMC Filter Class A – IP54

SKU: ATV21WU30N4

Specifications

CATEGORY: ​
PRODUCT BRAND: ​
PRODUCT NAME: ​
Variable Speed Drive – ATV21 – 3kw NAHP – 480V – EMC Filter Class A – IP54
PRODUCT NUMBER:
ATV21WU30N4
AVAILABILITY: ​
On-Demand

DESCRIPTION

Specifications

Main
Range of ProductAltivar 21
Product or Component TypeVariable speed drive
Product destinationAsynchronous motors
Product Specific ApplicationPumps and fans in HVAC
Assembly styleWith heat sink
Component nameATV21
EMC filterClass A EMC filter integrated
power supply voltage380…480 V – 15…10 %
Phase3 phase
Motor power kW3 kW
Line current4.9 A 480 V
6.2 A 380 V
Speed range1…10
Transient overtorque120 % of nominal motor torque +/- 10 % 60 s
Asynchronous motor control profileConstant voltage/frequency ratio
Quadratic voltage/frequency ratio
Current flux vector control (FVC) without speed feedback
Constant voltage/frequency ratio with automatic IR compensation
Energy saving ratio
Communication Port ProtocolModbus
Type of polarizationNo impedance
IP degree of protectionIP54 EN 60530
IP54 EN 61800-5-2
IP54 IEC 60529
IP54 IEC 61800-5-1
Option cardCommunication card APOGEE FLN
Communication card BACnet
Communication card LonWorks
Communication card METASYS N2
Complementary
power supply voltage limits323…528 V
power supply frequency50…60 Hz – 5…5 %
power supply frequency limits47.5…63 Hz
Apparent power5.5 kVA 380 V
maximum prospective line Isc5 kA
maximum continuous output current7.2 A 380 V
7.2 A 460 V
Maximum transient current7.9 A 60 s
Speed drive output frequency0.5…200 Hz
Nominal switching frequency12 kHz
Switching frequency12…16 kHz with derating factor
6…16 kHz adjustable
Speed accuracy+/- 10 % of nominal slip 0.2 Tn to Tn
Torque accuracy+/- 15 %
Regulation loopAdjustable PI regulator
Motor slip compensationAdjustable
Not available in voltage/frequency ratio motor control
Automatic whatever the load
diagnosticFor DC bus energized 1 LED (red)
Output voltage<= power supply voltage
insulationElectrical between power and control
recommended type of cable for mounting in an enclosureWith UL Type 1 kit 3 UL 508 cable 104 °F (40 °C), copper 75 °C / PVC
Without mounting kit 1 IEC cable 113 °F (45 °C), copper 70 °C / PVC
Without mounting kit 1 IEC cable 113 °F (45 °C), copper 90 °C / XLPE/EPR
Electrical connectionL1/R, L2/S, L3/T terminal 0.01 in² (6 mm²) / AWG 10
VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES terminal 0.00 in² (2.5 mm²) / AWG 14
Tightening torque11.51 lbf.in (1.3 N.m), 11.5 lb.in L1/R, L2/S, L3/T)
5.31 lbf.in (0.6 N.m) VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES)
SupplyInternal supply 24 V DC 21…27 V), <200 mA overload and short-circuit protection
Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, <10 mA overload and short-circuit protection
Analogue input number2
Analogue input typeVIA switch-configurable current 0…20 mA 242 Ohm 11 bits
VIA switch-configurable voltage 0…10 V DC 24 V max 30000 Ohm 11 bits
VIB configurable PTC probe 0…6 probes 1500 Ohm
VIB configurable voltage 0…10 V DC 24 V max 30000 Ohm 11 bits
Sampling durationF 2 ms +/- 0.5 ms discrete
R 2 ms +/- 0.5 ms discrete
RES 2 ms +/- 0.5 ms discrete
VIA 2 ms +/- 0.5 ms analog
VIB 2 ms +/- 0.5 ms analog
Response timeFLA, FLC 7 ms +/- 0.5 ms discrete
FLB, FLC 7 ms +/- 0.5 ms discrete
FM 2 ms +/- 0.5 ms analog
RY, RC 7 ms +/- 0.5 ms discrete
Accuracy+/- 1 % FM) for a temperature variation 60 °C
+/- 0.6 % VIA) for a temperature variation 60 °C
+/- 0.6 % VIB) for a temperature variation 60 °C
Linearity errorFM +/- 0.2 % output
VIA +/- 0.15 % of maximum value input
VIB +/- 0.15 % of maximum value input
Analogue output number1
Analogue output typeFM switch-configurable current 0…20 mA 500 Ohm 10 bits
FM switch-configurable voltage 0…10 V DC 470 Ohm 10 bits
Discrete output number2
Discrete output typeConfigurable relay logic FLA, FLC) NO – 100000 cycles
Configurable relay logic FLB, FLC) NC – 100000 cycles
Configurable relay logic RY, RC) NO – 100000 cycles
Minimum switching current3 mA 24 V DC configurable relay logic
Maximum switching current2 A 250 V AC inductive cos phi = 0.4 L/R = 7 ms FL, R)
2 A 30 V DC inductive cos phi = 0.4 L/R = 7 ms FL, R)
5 A 250 V AC resistive cos phi = 1 L/R = 0 ms FL, R)
5 A 30 V DC resistive cos phi = 1 L/R = 0 ms FL, R)
Discrete input typeF programmable 24 V DC level 1 PLC 3500 Ohm
R programmable 24 V DC level 1 PLC 3500 Ohm
RES programmable 24 V DC level 1 PLC 3500 Ohm
Discrete input logicNegative logic (sink) F, R, RES), >= 16 V, <= 10 V
Positive logic (source) F, R, RES), <= 5 V, >= 11 V
Acceleration and deceleration rampsAutomatic based on the load
Linear adjustable separately from 0.01 to 3200 s
Braking to standstillBy DC injection
Protection typeAgainst input phase loss drive
Break on the control circuit drive
Input phase breaks drive
Line supply overvoltage and undervoltage drive
Line supply undervoltage drive
Overcurrent between output phases and earth drive
Overheating protection drive
Overvoltages on the DC bus drive
Short-circuit between motor phases drive
Thermal power stage drive
Motor phase break motor
Thermal protection motor
With PTC probes motor
Against exceeding limit speed drive
Insulation resistance>= 1 mOhm 500 V DC for 1 minute
Frequency resolutionAnalog input 0.024/50 Hz
Display unit 0.1 Hz
Connector Type1 RJ45
Physical interface2-wire RS 485
Transmission frameRTU
Transmission Rate9600 bps or 19200 bps
Data format8 bits, 1 stop, odd even or no configurable parity
Number of addresses1…247
Communication ServiceTime out setting from 0.1 to 100 s
Monitoring inhibitable
Read device identification (43)
Write multiple registers (16) 2 words maximum
Write single register (06)
Read holding registers (03) 2 words maximum
markingCE
Operating positionVertical +/- 10 degree
Height13.39 in (340 mm)
Width9.06 in (230 mm)
Depth8.19 in (208 mm)
Product Weight21.27 lb(US) (9.65 kg)
Environment
Noise level55 dB 86/188/EEC
Dielectric strength3535 V DC between earth and power terminals
5092 V DC between control and power terminals
Electromagnetic compatibility1.2/50 µs – 8/20 µs surge immunity test level 3 IEC 61000-4-5
Conducted radio-frequency immunity test level 3 IEC 61000-4-6
Electrical fast transient/burst immunity test level 4 IEC 61000-4-4
Electrostatic discharge immunity test level 3 IEC 61000-4-2
Radiated radio-frequency electromagnetic field immunity test level 3 IEC 61000-4-3
Voltage dips and interruptions immunity test IEC 61000-4-11
standardsIEC 61800-3 environments 2 category C3
IEC 61800-5-1
IEC 61800-3 environments 2 category C2
IEC 61800-3 environments 1 category C3
EN 61800-3 environments 2 category C3
IEC 61800-3 environments 1 category C1
EN 61800-3
EN 61800-3 environments 2 category C1
EN 61800-3 environments 1 category C1
EN 61800-5-1
EN 61800-3 category C3
EN 61800-3 environments 2 category C2
IEC 61800-3 category C3
IEC 61800-3 category C2
EN 61800-3 environments 1 category C3
EN 61800-3 category C2
EN 61800-3 environments 1 category C2
EN 55011 class A group 1
IEC 61800-3
IEC 61800-3 environments 2 category C1
IEC 61800-3 environments 1 category C2
Product CertificationsCSA
UL
C-tick
NOM 117
Vibration resistance1 gn 13…200 Hz)EN/IEC 60068-2-8
1.5 mm 3…13 Hz)EN/IEC 60068-2-6
Shock resistance15 gn 11 ms IEC 60068-2-27
Pollution degree3 IEC 61800-5-1
Environmental characteristicClasses 3C1 IEC 60721-3-3
Classes 3S2 IEC 60721-3-3
Relative humidity5…95 % without condensation IEC 60068-2-3
5…95 % without dripping water IEC 60068-2-3
Ambient air temperature for operation14…104 °F (-10…40 °C) without derating)
104…122 °F (40…50 °C) with derating factor)
Ambient Air Temperature for Storage-13…158 °F (-25…70 °C)
Operating altitude<= 6561.68 ft (2000 m)
3280.84…9842.52 ft (1000…3000 m) limited to 2000 m for the Corner Grounded distribution network
Ordering and shipping details
Category22157-ATV212 1 – 25 HP 460 VOLT
Discount ScheduleCP4D
GTIN3389119406208
ReturnabilityNo
Country of originID
Contractual warranty
Warranty18 months
PRODUCT CATALOG: ​

Item reviews

Reviews

There are no reviews yet.

Only logged in customers who have purchased this product may leave a review.